搜索
PRODUCT
PRODUCT CENTER
RNR1-125-RCCB

| Application


ELECTRO-MAGNETIC RCCB RNR1-125 ( from 1 to 125A, up to 10KA ) meets any requirement for protection against residual current for all household, PV, EV charging, commercial and industrial low-voltage distribution systems. Saving 50% of space usage, it is easy to be assembled and works with the same series of compact circuit breakers together.




| Features


· Only 36mm for 1P+N and 72mm for 3P+N

· Protection against residual current and faulty wires

· Rated breaking capacity: 10kA

· Rated current: 25/40/63/80/100/125A

· Rated sensitivity current: 10/30/100/300mA

· Handle with padlock to protect from error operation

· Termianls with cover protection

Technical Data

| Electrical 


·Standard: IEC/EN 61008-1/62423

·Rated short-curcuit breaking capacity Inc: 10kA

·Residual current operating characteristic: AC, A, A[S], A[G], B Type

·Number of poles: 1P+N, 3P+N

·Rated current In: 25, 40, 63, 80, 100, 125A

·Rated residual operating current l△n (mA): 10, 30, 100, 300mA

·Rated residual non-operating current(mA): 0.5 I△n

·Rated voltage Un: 240/415VAC

·Rated frequency: 50/60Hz

·Rated impulse withstand voltage Uimp: 6kv

·Rated breaking capacity Im: 1000A

·Electrical life: 4000



| Mechanical


·Frame size: 45mm

·Device height: 77mm

·Device width: 36mm(1P+N), 72mm(3P+N)

·Installation: Quick fastening on 35mm Din rail

·Mechanical life: 10000

·Upper and lower terminals: Open mouthed/lift terminals

·Terminal protection: Finger and hand touch safe

·Terminal capacity: 4~50mm²

·Terminal fastening torque: 3.5Nm

·Degree of protection: IP20

·Operating temperature: -25℃ ~ +40℃

Dimensions(mm)
Specification
Connection Diagrams
Associated product column