| Application
The Busbar-Line LNBS system is a reliable interconnection of installation devices.No need for cutting,deburing or placing end-caps since they are already made on length and are fully isolated.This means in general a time saving up to 30% on making the busbars suited for the installation devices.There are all kinds of accessories available to make installation more suitable for the situation at hand.
| Features
·Small design with 10 mm² Cross Section
·Professional design works with Compact Series Circuit Breakers for user friendly installation
·Intergrated end-caps
·No deburring required
·No cutting back of copper required
| Electrical ·Regulations: DIN EN 60439-1|2000-08 ·According to: IEC 664 ·Rated conditional short-circuit current (Icc): 25kA/100Agl ·Disruptive strength: 36kV/mm ·Operating voltage: 500VAC ·Rated impulse withstand voltage (Uimp): 4kV ·Isolation group: According VDE 0110 TeiI 1 ·Busbar max. current (Is): 63A one side line-in ·Busbar max. current (Is): 100A* central line-in | | Mechanical ·Busbar material: E-Cu-ETP ·Isolation material: Ultramid PA6 glass fiber reinforced ·Form test: 125°C (after 1,8MPa) ·Glow wire test: 960° according IEC 60895-2-12 ·Flammability: Class V2 ·Comparative tracking index: 550 ·Climate stability: IEC 68-2 ·Overvoltage category: III ·Degree of soiling:2 ·Halogen free: According DIN EN 50267-2-2 ·Colors: Related to RAL7035 and RAL5012 ·Busbar cross-section: 10mm² |