| Application
The LNRN3 AUTO-RECLOSER is designed to automatically reclose the associated protective device after it has tripped, and being used for a variety of complex environments, especially in the field of unattended communication,centralized control,maneuver and network monitoring applications. It can be used in conjunction with RCCB/MCB/RCBO to realize the function of earth leakage, overload, short circuit protection with automatic self-reclosing.
| Features
·Compact body only 18mm
·Auto-reconnecting function with load poles earth leakage checking
·Work with MCB, RCCB, RCBO, etc., and remote control is available
·Auto/Manu operation is available
·Remote control of the specified low-voltage electrical equipments through PLC or platform with RS485connectiontoachievespecificap plications
| Electrical ·Power wiring: 1P+N single phase ·Rated voltage: 240V ·Rated frequency: 50/60 Hz ·Trip time: Trips<0.2s Reclose<0.3s (time delay excluded) ·Reclosing times: 3 times ·Reclose time delay: 1st: 10s; 2nd: 60s; 3th: 300s; 4th: locked ·Electrical-mechanical endurance: >10,000 times | | Mechanical ·Frame size: 45mm ·Device height: 80mm ·Device width: 18mm(1MU) ·Mounting: Quick fastening on 35mm DIN Rail according to IEC/EN 60715 ·Degree of protection, built-in: IP20 ·Terminal connection type: Cable ·Terminal protection: Finger and hand touch safe ·Terminal capacity: Rigid conductor up to 25mm² ·Busbar thickness: 0.8-2mm ·Terminal fastening torque: 4.0Nm ·Operating temperature: -25°C~+55°C ·Storage temperature: -40°C~+70°C ·Relative Humidity: ≤95% |